5: Communication Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
For manual entry:
CT Ratios
CT Numerator (Primary): 1 - 9999
CT Denominator (Secondary): 5 or 1 Amp
NOTE: This field is display only.
Either CT Multiplier (Scaling): 1, 10 or 100
OR Ratio: the ratio to be applied, and click Update CT
Current Full Scale: Display only.
PT Ratios
PT Numerator (Primary): 1 - 9999
PT Denominator (Secondary): 40 - 600
PT Multiplier (Scaling): 1, 10, 100, or 1000
Voltage Full Scale: Display only.
System Wiring
3 Element Wye; 2.5 Element Wye; 2 CT Delta
Example Settings:
For a CT of 2000/5A, set the following CT Ratios in the entry fields:
CT Numerator (Primary) 2000
CT Denominator (Secondary) 5
CT Multiplier 1
The Current Full Scale field will read 2000.
NOTE: You can obtain the same Current Full Scale by entering a CT Numerator of 200
and a CT Multiplier of 10.