Doc# E149701 7 - 14
7: Using the I/O Option Cards
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Minimum input voltage: 0V (input shorted to common)
Maximum input voltage: DC 150V (diode protected against polarity
reversal)
Filtering: De-bouncing with 50ms delay time
Detection scan rate: 100ms
Isolation: AC 2500V system to inputs
The general specifications are as follows:
Operating Temperature: (-20 to +70)° C
Storage Temperature: (-40 to +80)° C
Relative air humidity: Maximum 95%, non-condensing
EMC - Immunity Interference: EN61000-4-2
Weight: 1.3oz
Dimensions (inch) W x H x L: 0.72 x 2.68 x 3.26
External Connection: AWG 12-26/(0.129 - 3.31)mm
2
13 pin, 3.5mm pluggable terminal block
7.7.2: Default Configuration:
The Shark® 200 meter automatically recognizes the installed Option card during
power up. If you have not programmed a configuration for the card, the unit defaults
to the following outputs:
Status Inputs Defaulted to Status Detect
Pulse Outputs Defaulted to Energy Pulses
Pulse Channel 1 1.8 +Watt-hours per pulse
Pulse Channel 2 1.8 -Watt-hours per pulse