Electro Industries Shark 200T Especificações Página 79

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 298
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 78
Doc# E149701 5 - 1
5: Communication Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
5: Communication Installation
5.1: Shark® 200 Meter Communication
The Shark® 200 meter provides two independent Communication ports. The first
port, Com 1, is an optical IrDA port. The second port, Com 2, provides RS485
communication speaking Modbus ASCII, Modbus RTU, and DNP 3.0 protocols.
Additionally, the Shark® 200 meter has optional communication cards: the Fiber
Optic communication card and the 10/100BaseT Ethernet communication card. See
chapters 7 and 8 for more information on these options.
5.1.1: IrDA Port (Com 1)
The Shark® 200 meter’s Com 1 IrDA port is on the face of the meter. The IrDA port
allows the unit to be read and programmed without the need of a communication
cable. Just point at the meter with an IrDA-equipped laptop PC to configure it.
NOTES:
• Settings for Com 1 (IrDA Port) are configured using Communicator EXT
TM
software.
• This port only communicates via Modbus ASCII Protocol.
• Refer to Appendix D for instructions on using EIG’s USB to IrDA Adapter.
5.1.2: RS485 / KYZ Output (Com 2)
Com 2 provides a combination RS485 and an Energy Pulse Output (KYZ pulse).
See Chapter 2, Section 2.2 for the KYZ Output specifications; see Chapter 6, Section
6.4 for pulse constants.
Vista de página 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 297 298

Comentários a estes Manuais

Sem comentários