Doc# E149701 7 - 4
7: Using the I/O Option Cards
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
7.3: Configuring Option Cards
CAUTION! FOR PROPER OPERATION, RESET ALL PARAMETERS IN THE UNIT
AFTER HARDWARE MODIFICATION.
The Shark® 200 meter auto-detects any Option cards installed in it. You configure the
Option cards through Communicator EXT
TM
software. Refer to Chapter 5 of the
Communicator EXT
TM
User Manual for detailed instructions.
The following sections describe the available Option cards.
7.4: 1mA Output Card (1mAOS)
The 1mA card transmits a standardized bi-directional 0-1mA signal. This signal is
linearly proportional to real-time quantities measured by the Shark® 200 meter. The
outputs are electrically isolated from the main unit.
7.4.1: Specifications:
The technical specifications at 25° C at 5k load are as follows:
Number of outputs: 4 single ended
Power consumption: 1.2W internal
Signal output range: (-1.2 to +1.2)mA
Max. load impedance: 10k
Hardware resolution: 12 bits
Effective resolution: 14 bits with 2.5kHz PWM
Update rate per channel: 100ms
Output accuracy: ± 0.1 % of output range (2.4mA)
Load regulation ± 0.06 % of output range (2.4mA) load step of 5k
@ ± 1mA
Temperature coefficient ± 30nA/° C
Isolation: AC 2500V system to outputs
Reset/Default output value: 0mA
: